The BT 500-IS-1 Cable Fault Converter is mainly used for converting high-resistive cable faults in signal, control and telecommunication cables into low-resistive ones.
Its source of adjustable voltage 0 to 2 kV has a balanced output, i. e. a faulty pair of wires can be connected to its output terminal balanced to earth.
In conjunction with a special Sheath Pre-locating Device of type MVG 5, sheath faults can be pre-located. Using this accessory device, the following measurements can be taken:
- Sheath fault pre-location on shielded telecommunication and control cables with PVC or PE-type sheath
- Sheath fault prelocation on shielded medium-high voltage cables with PVC sheath (test voltage up to 2kV)
Pin pointing is carried out by means of the Earth Fault Locating Device ESG 80-2 by the method of measuring the step voltage. Moreover our new Cable Fault Converter BT 500-IS-1 has some more special features such as:
- Continuously adjustable output voltage in voltage ranges 500, 1000, 2000 V
- Floating Potential at either outputs
- Protection against overload by voltage and current control
- Fault location at reduced power to prevent damages to adjacent wires or cables
- Indication of voltage and current by two analog indicating instruments
- Automatic discharge unit provides for removal of residual charge and for earthing the test object
- Clock-controlled operation of the voltage source to prevent the drying-out of faults when pin pointing sheath faults
Accessory equipment:
- Earth Fault Locating Device ESG 80-2
- Earth spikes with measuring leads EEB
- Sheath Fault Pre-locating Device MVG 5
- Emergency-off switch NAG 1 for stand-alone operation
- Emergency-off switch NAG 2 for operation with MVG 5
|